Store in a cool, dry and well ventilated area. Keep containers closed. Wash contaminated clothes before re-use. Wash thoroughly after handling.
For more information, see the Safety Data Sheet.
Prepare cleaning solution using potable water free of residual chlorine or other oxidizing agents. (RO permeate or DI water is preferred). Do not use hard water. Add 1-2 gallons of AWC UF-437 to every 100 gallons of water (1-2 % solution), depending on severity of fouling. Water must be heated to the maximum temperature allowed by the module manufacturer. Adjust pH to the highest pH allowable by the membrane manufacturer. If pH needs to be adjusted downwards, use HCl (31% Muriatic acid) and add only 0.1% by volume at a time. Mix thoroughly by recirculation before checking pH; repeat addition as necessary. If pH needs to be adjusted upwards, use NaOH (50% Caustic Soda) and add only 0.1% by volume at a time. Mix thoroughly by recirculation before checking pH; repeat addition as necessary.
Circulate cleaning solution throughout the modules, with the filtrate valve closed, in the feed direction for 30 min (for tubular designs). Reverse the direction of flow; recirculate for 30 more minutes. Repeat as necessary until desired cleaning results are achieved. AWC UF-437 should be added as necessary to the cleaning solution to maintain the pH range. Optimal iron removal occurs at pH of 9.0–10.5. For systems that allow back flushing, back flush with cleaning solution from the filtrate to the feed for 15 minutes. After the cleaning is finalized the modules must be flushed with MF/UF filtrate.