Under which conditions can antiscalants cause RO membrane fouling?
Reverse Osmosis Antiscalants can cause membrane fouling in Reverse Osmosis systems under the following conditions:
Fungal growth in the antiscalant – some antiscalants contain impurities that can provide the necessary nutrients and carbon for biogrowth. It is not uncommon to find fungal growth in polymer-based antiscalants. The growth in the drum can seed growth on the membrane surface. Reputable manufacturers manufacture higher purity products and use NSF approved anti-fungal preservatives to prevent these issues.
The dosing point too close to acid addition point – pH is typically adjusted using concentrated sulfuric acid. In the absence of good mixing, the acid will temporarily form a separate phase due to its very high density relative to water. If the antiscalant is dosed immediately after the acid dosing point, it can be hydrolyzed by the strong acid. Certain polymer-based antiscalants are very susceptible to this degradation.
Incompatibility with water quality – some antiscalants do not have good tolerance to iron and aluminum. Such antiscalants will form an insoluble complex with these metals and precipitate on the RO membrane surface.
Very high hardness or very high antiscalant dosage – antiscalants carry a higher negative charge than typical scale forming anions such as carbonate or phosphate; so they have a strong attraction to calcium and magnesium. During threshold inhibition, this attraction to calcium/magnesium causes adsorption to forming clusters, and interferes with the formation of a stable nucleus. However, when hardness concentrations are very high, the antiscalants itself can form an insoluble calcium-antiscalant salt. This is problematic because once the active inhibitor precipitates, other scales will also precipitate. Hardness impacts all antiscalants, regardless of whether they are polymer or phosphonate-based. AWC’s Proton antiscalant projection software can predict this salt formation, and can therefore predict maximum recovery at a given temperature and pH.
Quality control issues – in some cases, manufacturing issues can cause certain polymer-based antiscalants to form insoluble gels on the membrane surface. It is therefore imperative to use antiscalants only from reputable suppliers.
Related FAQs
You may also be interested in reading more about the following FAQs.
A few weeks ago, we pickled all RO membranes in our trains with sodium...
When you mix sodium metabisulfite in water, you form a sodium bisulfite solution:
$${Na_2S_2O_5 + H_2O \Leftrightarrow 2NaHSO_3}$$$${NaHSO_3 \Leftrightarrow Na^+ + HSO{_3}{^-}}$$
Bisulfite is in...
Can chlorine dioxide be used effectively in place of sodium hypochlori...
Chlorine dioxide is a highly potent biocide that has a higher efficacy than hypochlorite in destroying protozoa, bacteria and viruses, without allowing them to build a tolerance. It is effective ove...
Can hydrogen peroxide be used effectively in place of sodium bisulfite...
Q:Can hydrogen peroxide be used effectively in place of sodium bisulfite for dechlorination of seawater RO feedwater? We are concerned about dissolved oxygen levels in the c...
Can I use citric acid to descale/clean a reverse osmosis (RO) Membrane...
Citric acid is an organic acid that is often used for removal of calcium carbonate scale and iron hydroxide. Citric acid is not very effective at removing phosphate salts such as calcium and iron ph...
Can Sulfuric acid or HCl be used with the addition of Citric acid for ...
Using citric acid is very expensive. If the water source contains oxygen, has been exposed to oxidizers, or ferric based coagulants have been used, the iron will be in the ferric state and can typical...